beautypg.com

Bristol controlwave micro, Wiring plan, Parameter – VEGA VEGAFLEX 86 Modbus and Levelmaster protocol User Manual

Page 94: 11 supplement

background image

94

11 Supplement

VEGAFLEX 86 • Modbus and Levelmaster protocol

41848-EN-130314

Bristol ControlWave Micro

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

3

13

45

2o

ff

on

( )

(

)

(-)

(-)

+8

+30 Vdc

to

GND

1 +SV

RS

485 on COM1

2 RX-

5 RXT

6 TXT

3 TX-

4 GND

7 not used

8 not used

Fig. 52: Connection of VEGAFLEX 86 to RTU Bristol ControlWave Micro
1 VEGAFLEX 86

2 RTU Bristol ControlWave Micro

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

2 (FC4)

RTU Data Type

32-bit registers as 2 16-bit registers

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGAFLEX

86.
Address 1303 must hence be entered as register address for 1302 for RTU Bristol ControlWave

Micro.