beautypg.com

VEGA VEGAFLEX 86 Modbus and Levelmaster protocol User Manual

Page 56

background image

56

7 Setting up sensor and Modbus interface with PACTware

VEGAFLEX 86 • Modbus and Levelmaster protocol

41848-EN-130314

Linear

Spherical tank

Horizontal cylindrical tank

You must enter the following vessel dimensions with non-linear condi-

tions:

Height of the socket h

Vessel height D

In this window you can adjust the output signal. When the function is

inactive, you can change the settings via the "Extended adjustment".

These settings allow you to optimize the sensor. With them you can

compare a sounded distance with the indicated value and correct it, if

necessary.
Probe immersed in the liquid (covered)

Select whether or not the probe is immersed in the medium.
Measured distance to the medium

If the probe is immersed in the medium, you can enter here the meas-

ured distance to the medium.
Displayed distance correct?

Is the displayed distance value correct? If you have the possibility, you

can enter here the sounded distance to the medium.
False signal suppression

With this function you can carry out the automatic false signal sup-

pression. We recommend carrying out false signal suppression in any

case.

When the setup of the instrument is finished, additional settings can

be made. These are various backups and the locking of the instru-

ment against unauthorised or inadvertent adjustment.
Prepare a backup file of the instrument parameter adjustment?

For backup purposes, the current parameter adjustment of the instru-

ment is stored in a file. You can use this file later on to restore the

instrument parameter adjustment. The complete data set is down-

loaded from the device. This procedure can last several minutes.
Create instrument documentation?

This function is used to print or create a PDF file of the current param-

eter adjustment. To read the PDF file, you need a suitable program

(for example Acrobat Reader). To print or create the PDF file, all data

are downloaded from the device. For this function, the full version

of the DTM Collection is required. This procedure can last several

minutes.
Store echo curve of the setup in the sensor?

Have you completed the initial setup of the instrument? In such case,

we recommend storing the current signal conditions in the device for

later instrument tests and diagnostics.

Step 5 of 7

Setting - Output signal

Step 6 of 7

Sensor optimization

Step 7 of 7

Additional settings