VEGA VEGAFLEX 86 Modbus and Levelmaster protocol User Manual
Page 41
41
6 Set up with the display and adjustment module
VEGAFLEX 86 • Modbus and Levelmaster protocol
41848-EN-130314
In the menu item "Lock/unlock adjustment", you can protect the
sensor parameters against unauthorized modification. The PIN is
activated/deactivated permanently.
The following adjustment functions are possible without entering the
PIN:
•
Select menu items and show data
•
Read data from the sensor into the display and adjustment mod-
ule.
Caution:
With active PIN, adjustment via PACTware/DTM as well as other
systems is also blocked.
You can change the PIN number under "Additional adjustments -
PIN".
This menu item enables the setting of the requested national lan-
guage.
In the delivery status, the sensor is set to the ordered national lan-
guage.
In this menu item, you define the indication of the measured value
on the display. You can display two different measured values. In this
menu item, you define measured value 1.
The default setting for the displayed value 1 is "Filling height Level".
In this menu item, you define the indication of the measured value
on the display. You can display two different measured values. In this
menu item, you define measured value 2.
The default setting for the displayed value 2 is the electronics tem-
perature.
Lock/unlock setup - Ad-
justment
Display - Menu language
Display - Displayed value
1
Display - Displayed value
2