9 Diagnostics and service

VEGAFLEX 81 • HART - integrated accumulator

44640-EN-130430

9.6 Exchanging the cable/rod

If necessary, the cable or rod (measuring part) of the probe can be

exchanged.
Loosen the rod or cable with a fork wrench, wrench size 7 (rod ø 8,

cable ø 2 and 4) or wrench size 10 (rod ø 12).
1. Loosen the rod or cable with a fork wrench applied to the flat

surface, provide counterforce with another fork wrench.

2. Unscrew the loosened rod or cable manually.
3. Insert the new measuring rod carefully by hand with a twisting

motion into the opening of the process fitting.

4. Continue screwing in the rod manually into the opening of the pro-

cess fitting.

5. Exert counterforce with the second fork spanner and tighten the

rod or cable on the flat surfaces with the following torque.
Rod ø 8, cable ø 2 and 4: 6 Nm (4.43 lbf ft)
Rod ø 12: 10 Nm (7.37 lbf ft)

Fig. 35: Exchange cable or rod

Information:

Please keep the stated torque so that the max. tensile strength

remains.
6. Enter new probe length and then carry out a fresh adjustment

(see "Setup procedure, Carrying out min. adjustment - Carrying

out max. adjustment").

The rod or cable of the probe can be shortened individually.

1. Mark the requested length with mounted measuring rod.
2. Cable: Loosen the pins on the gravity weight (hexagon 3)
3. Cable: remove the pins
4. Cable: Pull the cable out of the gravity weight
5. Shorten the cable/rod with a cut-off wheel or metal saw at the

marking. Take note of the specifications in the following illustration

when shortening the cable.

Exchanging the cable/rod

Shorten cable/rod