VEGA VEGAFLEX 81 HART - integrated accumulator User Manual
Page 45

45
6 Set up with the display and adjustment module
VEGAFLEX 81 • HART - integrated accumulator
44640-EN-130430
Menu item
Default value
Current output - Max.
20.5 mA
Current output 2 - Output
variable
Second HART varia-
ble (SV)
Distance - Level
Current output 2 - Output
characteristics
0 … 100 % correspond to 4 … 20 mA
Current output 2 - Reac-
tion in case of failure
≤ 3.6 mA
Current output - Min.
3.8 mA
Current output - Max.
20.5 mA
Third HART variable
(TV)
Measurement certainty, level
Fourth HART variable
(QV)
Electronics temperature
Display
Menu item
Default value
Language
Order-specific
Displayed value 1
Filling height Level
Displayed value 2
Electronics temperature
Backlight
Switched off
Diagnostics
Menu item
Default value
Status signals - Function
control
Switched on
Status signals - Out of
specification
Switched off
Status signals - Mainte-
nance
Switched off
Device memory - Echo
curve memory
Stopped
Device memory - Meas-
ured value memory
Started
Device memory - Meas-
ured value memory
- Measured values
Distance level, percentage value level, reliability
level, electronics temperature
Device memory - Meas-
ured value memory
- Recording in time in-
terval
3 min.