beautypg.com

VEGA VEGAFLEX 81 HART - integrated accumulator User Manual

Page 44

background image

44

6 Set up with the display and adjustment module

VEGAFLEX 81 • HART - integrated accumulator

44640-EN-130430

Menu item

Default value

Min. adjustment - Level

Distance: Probe length - take dead band into ac-

count

Accept adjustment of the

level measurement?

Yes

Max. adjustment - In-

terface

100 %

Max. adjustment - In-

terface

Distance: 0.000 m(d) - note blocking distances

Min. adjustment - In-

terface

0 %

Min. adjustment - In-

terface

Distance: Probe length - take dead band into ac-

count

Integration time - Level

0.0 s

Integration time - Inter-

face

0.0 s

Linearization type

Linear

Linearization - Socket

correction

0 mm

Linearization - Vessel

height

Probe length

Scaling size - Level

Volume in l

Scaling unit - Level

Litres

Scaling format - Level

Without decimal positions

Scaling level - 100 %

correspond to

100

Scaling level - 0 % corre-

spond to

0

Accept scaling of the lev-

el measurement

Yes

Scaling size - Interface

Volume

Scaling unit - Interface

Litres

Scaling format - Interface Without decimal positions
Scaling interface - 100 %

correspond to

100

Scaling interface - 0 %

correspond to

0

Current output, output

variable
First HART variable (PV)

Lin. percent - Level

Current output - Output

characteristics

0 … 100 % correspond to 4 … 20 mA

Current output - Reac-

tion in case of failure

≤ 3.6 mA

Current output - Min.

3.8 mA