6 Set up with the display and adjustment module
VEGAFLEX 81 • HART - integrated accumulator
44640-EN-130430
With a reset, certain parameter adjustments carried out by the user
are reset.
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-
ment from the factory incl. the order-specific settings. A created false
signal suppression, user-programmable linearization curve as well as
the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special pa-
rameters to the default values of the respective instrument. A created
false signal suppression, user programmable linearization curve as
well as the measured value memory will be deleted.
The following table shows the default values of the instrument. De-
pending on the instrument version or application, all menu items may
not be available or some may be differently assigned:
Setup
Menu item
Default value
Block operation
Released
Measurement loop name Sensor
Units
Distance unit: mm
Temperature unit: °C
Probe length
Length of the probe Ex factory
Medium type
Liquid
Applications
Level, vessel
Medium, dielectric con-
stant
Water-based, > 10
Superimposed gas
phase
Yes
Dielectric figure, upper
medium (TS)
1.5
Tube inner diameter
200 mm
Max. adjustment - Level 100 %
Max. adjustment - Level Distance: 0.000 m(d) - note blocking distances
Min. adjustment - Level
0 %
Additional adjustments
- Reset