9 Diagnostics and service

MINITRAC 31 • 4 … 20 mA/HART - four-wire

43389-EN-131119

Error

Cause

Rectification

4 … 20 mA signal

missing

Electrical connec-

tion faulty

Check connection according to

chapter "Connection steps" and if

necessary, correct according to chap-

ter "Wiring plan"

Voltage supply

missing

Check cables for breaks; repair if nec-

essary

Operating voltage

too low or load re-

sistance too high

Check, adapt if necessary

Current sig-

nal greater than

22 mA or less

than 3.6 mA

Instrument on fail-

ure message

Note error message on the display

and adjustment module

The following table describes possible faults that may not generate an

error message:

Error

Cause

Rectification

The instrument

signals covered

without covering

with the medium
The instrument

signals covered

with covering with

the medium

Voltage supply

missing

Check cables for breaks; repair if nec-

essary

Operating voltage

too low or load re-

sistance too high

Check, adapt if necessary

Electrical connec-

tion faulty

Check connection according to

chapter "Connection steps" and if

necessary, correct according to chap-

ter "Wiring plan"

Electronics de-

fective

Change the switching behaviour of the

sensors under "Diagnosis/Simulation".

If the instrument does not switch over,

send it in for repair.

Buildup on the in-

ner wall of the

vessel

Remove buildup
Check the Delta I value.
Improve the switching threshold - car-

ry out a double point adjustment

Current sig-

nal greater than

22 mA or less

than 3.6 mA

Electronics mod-

ule in the sensor

defective

Note error messages on the display

and adjustment module

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Setup" must be carried out again or must

be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven

days a week around the clock.

Check output signal

(level detection)

Reaction after fault recti-

fication

24 hour service hotline