4 Mounting

MINITRAC 31 • 4 … 20 mA/HART - four-wire

43389-EN-131119

4.2 Mounting instructions

Note:

Along with the planning, our specialists will analyse the conditions of

the measurement loop to dimension the radiation source (isotope)

accordingly.
You get a "Source Sizing" document specifying the required source

activity and containing all relevant mounting information for your

measuring point.
You must follow the instructions of this "Source Sizing" document in

addition to the following mounting instructions.
The following mounting information is applicable as long as there is

nothing else specified in the "Source Sizing" document.
You can find information on protective barriers and the mounting

of the corresponding source container in the operating instructions

manual of the source container, e.g. VEGASOURCE.
You can mount the MINITRAC 31 in any position. If you have ordered

your instrument with a lead cover as a protection against ambient

radiation (optionally), the the sensor is shielded laterally against X-ray

radiation. In this case, the radiation can only penetrate frontally.
Fasten the sensors in such a way that they cannot fall out of the

holder.
Direct the exit angle of the source container to the MINITRAC 31.
Mount the source container as close as possible to the vessel. If there

are gaps, secure the area with a safety fence and protective grating

so that no one can reach into the dangerous area.
Point level detection

For level detection, the sensor is generally mounted horizontally at the

height of the requested limit level. Make sure that there are no struts

or reinforcements at this position in the vessel.
Direct the exit beam of the source container exactly towards the

measuring range of MINITRAC 31.

Installation position