7 Set up with the display and adjustment module
MINITRAC 31 • 4 … 20 mA/HART - four-wire
43389-EN-131119
After a change, all safety-relevant parameters must be verified. For
this purpose, a character string comparison must be carried out. This
is used to check the character respresentation and the communica-
tion channels.
Confirm if the two character strings are identical. The verification texts
are provided in German and with all other menu languages in English.
In a second step, all modified safety-relevant parameters are listed.
Confirm the modified values.
If the described process of parameter adjustment was run through
completely and correctly, the instrument will be locked and hence
ready for operation.
Otherwise the instrument remains in the released and hence unsafe
condition.
The main menu is divided into five sections with the following func-
tions:
Setup: Settings, e.g. for measurement loop name, isotope, applica-
tion, background radiation, adjustment, signal output
Display: Settings, for example language, measured value display
Diagnosis: Information, for example, of device status, peak value,
simulation
Additional adjustments: Instrument unit, reset, date/time, copying
function
Info: Instrument name, hardware and software version, date of manu-
facture, instrument features
Check if the correct language is already set for the display. If not, you
can change the language in the menu item "Display/Language".
Main menu
Procedure