VEGA MINITRAC 31 4 … 20 mA_HART - four-wire With SIL qualification User Manual
Page 40
40
7 Set up with the display and adjustment module
MINITRAC 31 • 4 … 20 mA/HART - four-wire
43389-EN-131119
Menu
Menu item
Default value
Setup
Measurement loop name
Sensor
Isotope
Cs-137
Application
Level
Adjustment
0 %, 100 %
Linearization
0 ct/s ≙ 100 %
90000 ct/s ≙ 0 %
Background radiation
0 ct/s
Unit of the process value
%
Temperature unit
°C
Damping
60 s (manually)
Real value correction
0
Current output
Activated
Current output mode
4 … 20 mA, < 3.6 mA
Current output Min./Max.
Min. current 3.8 mA, max. current 20.5 mA
Reference value - Relay
None
Mode
Overfill protection
Upper switching point -
Process value
0 %
Lower switching point -
Process value
0 %
Upper switching point -
Temperature
50 °C
Upper switching point -
Temperature
25 °C
Block adjustment
Released
Address - Summation
Slave
free
Display
Language
Selected language
Displayed value
Pulse rate
Display unit
ct/s
Additional adjustments
Temperature unit
°C
Linearisation curve
Empty
HART mode
Standard
Address 0
With this function you can select the mode.
The sensor offers the HART modes standard and multidrop.
If the measured value is outputted via the 4 … 20 mA output, you
must not switch over to HART Multidrop.
The mode 'Standard', with fixed address 0 (factory setting), means
output of the measured value as 8/16 mA signal.
Additional adjustments -
HART mode