6 Adjustment with the display and adjustment module PLICSCOM

VEGADIF 65 • 4 … 20 mA/HART

36128-EN-130417

2. Confirm the menu "Basic adjustment" with [OK], the menu item

"Units of measurement" will be displayed.

3. Activate the selection with [OK] and select the requested unit with

[->] (in the example m).

4. Confirm with [OK], the submenu "Density unit" appears.

Unit of measurement

Density unit

kg/dm³
pcf

5. Select the requested unit, e.g. kg/dm³ with [->] and confirm with

[OK], the submenu "Density" appears.

Unit of measurement

Density
0001000
kg/dm³

6. Enter the requested density value with [->] and [+], confirm with

[OK] and move to position correction with [->].

The adjustment unit is thus switched over from bar to m.
Proceed as follows to select the temperature unit:
1. Activate the selection with [OK] and select "Temperature unit

with [->].

2. Activate the selection with [OK] and select the requested unit with

[->] (e.g. °F).

3. Confirm with [OK].
The temperature unit is hence switched over from °C to °F.

The position correction compensates the influence of the installation

position of the instrument on the measured value. In this menu item,

the offset value as well as the current measured value are displayed.
Proceed as follows:
1. Activate in the menu item "Position correction" the selection with

[OK].

Position correction
Offset

DP

=
0.0000 bar
0.0035 bar

2. Select with [->], e.g. to accept the actual measured value

0.0035 bar.

Position correction
Accept current measured

value?

Accept
Edit

3. Confirm with [OK].

Position correction

Position correction