beautypg.com

VEGA VEGADIF 65 4 … 20 mA_HART User Manual

Page 35

background image

35

5 Connecting to power supply

VEGADIF 65 • 4 … 20 mA/HART

36128-EN-130417

4. Remove approx. 10 cm of the cable mantle, strip approx. 1 cm

insulation from the individual wires

5. Insert the cable into the sensor through the cable entry
6. Lift the opening levers of the terminals with a screwdriver (see

following illustration)

7. Insert the wire ends into the open terminals according to the wir-

ing plan

8. Press down the opening levers of the terminals, you will hear the

terminal spring closing

9. Check the hold of the wires in the terminals by lightly pulling on

them

10. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation

11. Tighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

12. Screw the housing cover back on
The electrical connection is hence finished.

Fig. 34: Connection steps 6 and 7

Proceed as follows:
1. Loosen the four screws on the housing base with an Allen key

size 4

2. Remove the mounting plate from the housing socket

IP 68 version with exter-

nal housing