beautypg.com

9 supplement, 1 technical data – VEGA VEGAMET 381 Ex User Manual

Page 31

background image

31

9 Supplement

VEGAMET 381 Ex • 4 … 20 mA signal conditioning instrument

30418-01-131025

9 Supplement

9.1 Technical data

General data
Series

Instrument for mounting into front panel, switching cabi-

net or housing

Weight

400 g (0.882 lbs)

Housing material

plastic ABS/POM

Connection terminals

Ʋ Type of terminal

Screw terminal

Ʋ Max. wire cross-section

1.5 mm² (AWG 16)

Voltage supply
Operating voltage

20 … 253 V AC, 50/60 Hz, 20 … 253 V DC

Max. power consumption

12.4 VA, 4 W

Sensor input
Number of sensors

1 x 4 … 20 mA

Type of input (switchable)

Ʋ mode active

Sensor is powered by VEGAMET 381 Ex

Ʋ mode passive

Sensor has an own power supply

Measured value transmission

4 … 20 mA

Deviation

Ʋ Accuracy

±20 µA (0.1 % of 20 mA)

Terminal voltage mode active

20 … 15 V at 4 … 20 mA

Current limitation mode active

30 mA

Internal resistance mode passive

< 250 Ω

Detection line break

≤ 3.6 mA

Detection shortcircuit

≥ 21 mA

Adjustment range

Ʋ Empty adjustment

3.8 … 20.2 mA

Ʋ Full adjustment

4.1 … 20.5 mA

Ʋ min. adjustment delta

300 µA

Connection cable to the sensor

two-wire standard cable (screening recommended)

Relay outputs
Quantity

2 x operating relay, 1 x fail safe relay

Contact

Floating spdt

Contact material

AG NI 0.15 hard gold-plated

Switching voltage

min. 10 mV DC, max. 250 V AC/DC