4 Mounting
4.1 General instructions
The module cards of VEGALOG 571 can only be mounted into
the 19" carrier BGT LOG 571. It is provided with a special bus
board for data transmission between CPU and the individual
peripheral cards (LOGBUS). The carrier is designed for
mounting into a switching cabinet or 19" housing.
The plug position for the individual cards is individually
selectable, the system saves the card positions when switch-
ing on.
Note:
The plug positions must not be changed after the parameter
adjustment because measurement loops that have already
been set up would otherwise have to be reconfigured.
4.2 Carrier
By means of the plug connectors on the bus board, a fixed
pattern is created for the use of the modules. This ensures that
each module card is plugged into the multipoint connector and
also into its LOGBUS socket.
l
Number of subunits (TE)
-
84 TE, thereof one 4 TE blind cover on module 1
l
Width of the module cards
-
5 TE for CPU and peripheral cards
-
10 TE for VEGASTAB 593
l
Number of module cards in the BGT LOG 571
-
max. 16 pcs. (e.g. 1x VEGASTAB 693, 1x CPU and
13x peripheral cards)
A VEGALOG 571 in the maximum configuration consists of
two completely equipped carriers which are connected to each
other via a pluggable bus cable (see "Chapter Electrical
connection"). Because the bus cable may not be lengthened,
the two carriers must be mounted directly above one another.
Note:
In the following cases, it is recommended to mount a 19"
ventilator to avoid a temperature increase in VEGALOG.
l
If more than one carrier is placed above the other
l
If air cannot circulate in the area of the carrier
10
VEGALOG 571 - CPU and carrier
Mounting