3 filing of measured value as 4 byte float – VEGA Modbus-TCP, ASCII protocol User Manual
Page 6

6
1 Function as Modbus-TCP server
Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30768-EN-130701
Register ad-
dress in
Modicon
Temporary memory of VE-
GAMET/PLICSRADIO (1 bit)
Temporary memory of VE-
GAMET 391 (1 Bit)
10001
Fail safe relay
Fail safe LED
10002
Relay 1
Relay 1
10003
Relay 2
Relay 2
10004
Relay 3
Relay 3
10005
----
Relay 4
10006
----
Relay 5
10007
----
Relay 6
1.3 Filing of measured value as 4 Byte Float
The filing of measured values in the temporary memory is always
sorted according to PC/DCS output number. The following chart
shows the addressing of the temporary memory via Modbus. The
values are accessed via FC 3 and 4. The status information is also
transmitted as float value. 8 byte are needed for one output, corre-
sponding to 4 registers.
Information:
Note: A float value comprises 2 registers, i.e. a total of 4 bytes!
Register address in
Modicon
Temporary memory of VEGAMET/PLICSRADIO
(2 words = 4 byte)
31001
PC/DCS output 1: Measured value
31003
PC/DCS output 1: Status
31005
PC/DCS output 2: Measured value
31007
PC/DCS output 2: Status
31009
PC/DCS output 3: Measured value
31011
PC/DCS output 3: Status
31013
PC/DCS output 4: Measured value
31015
PC/DCS output 4: Status
31017
PC/DCS output 5: Measured value
31019
PC/DCS output 5: Status
31021
PC/DCS output 6: Measured value
31023
PC/DCS output 6: Status
Register address in
Modicon
Temporary memory of VEGASCAN (2 words =
4 byte)
31001
PC/DCS output 1: Measured value
31003
PC/DCS output 1: Status
31005
PC/DCS output 2: Measured value
31007
PC/DCS output 2: Status
31009
PC/DCS output 3: Measured value