2 ASCII protocol
Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30768-EN-130701
Number of bytes
Character
Identifier
1
%
Begin
1 … 3
001 … 030 or 1 … 30
Separator
1
L or I
Quantity
1 … 3
001 … 030 or 1 … 30
End identification
1
CR
•
Identifier: "%" (1 character)
•
Start: No. of the requested PC/DCS output (1 … 3 characters)
•
Separator: "L" or "I" (1 sign)
•
Quantity: Number of requested PC/DCS outputs (1 … 3 signs)
•
End identification: Carriage Return CR (1 sign)
Total length of the telegram: 5 … 9 characters
"N"-times repetition of the following telegram
Number of bytes
Character
T1
1
=
DCS no.
3
001 … 030
T2
1
#
Value
5 … 6
-067.3
T3
1
%
End identification
1
CR
•
T1: "=" (1 character)
•
DCS no.: No. of the PC/DCS output as 3-digit decimal number
•
T2: "#" (1 character)
•
Value: Numerical value of the PC/DCS output or with interferred
measured value the text "FAULT"
Formatting of the value:
Character
Meaning
1
"- ": Minus with negative numbers
" ": Space with positive numbers
2 … 4
3-digit number
5
".": Decimal point
6
1-digit number (after the decimal point)
•
T3: "%" (1 character)
•
End identification: Carriage Return CR (1 sign)
Total length of the telegram: "Number"*12 … 13 signs
Note:
The % sign is a separator, not the unit %
Enquiry:
%001L003
Enquiry of the control
system
Reply from the signal
conditioning instrument
Example: