2 ASCII protocol

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

Start: No. of the requested PC/DCS output (1 … 3 characters)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: 3 … 5 characters

Number of bytes

Character

T1

1

=

DCS no.

3

001 … 030

T2

1

#

Value

7

-000673

T3

1

#

Unit

0 … n

xxx

End identification

1

CR

T1: "=" (1 character)

DCS no.: No. of the PC/DCS output as 3-digit decimal number

T2: "#" (1 character)

Value: Numerical value of the PC/DCS output or with interferred

measured value the text "FAULT"

Formatting of the value:

Character

Meaning

1

"- ": Minus with negative numbers
" ": Space with positive numbers

2 … 7

6-digit number after the decimal point

T3: "#" (1 character)

Unit: Unit as text (0 … n unit)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: 14 characters+Unit character
Enquiry:

?001
Answer:

=001# 000673#%

? Block enquiry

All assigned PC/DCS values in the instrument are delivered as reply

to the block enquiry. The measured value is transmitted with six deci-

mal places without decimal point and with unit.

Number of bytes

Character

Identifier

1

?

End identification

1

CR

Identifier: "?" (1 character)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: 2 characters

Reply from the signal

conditioning instrument

Example:

Enquiry of the control

system