VEGA Modbus-TCP, ASCII protocol User Manual
Page 21
21
2 ASCII protocol
Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30768-EN-130701
•
Start: No. of the requested PC/DCS output (1 … 3 characters)
•
End identification: Carriage Return CR (1 sign)
Total length of the telegram: 3 … 5 characters
Number of bytes
Character
T1
1
=
DCS no.
3
001 … 030
T2
1
#
Value
7
-000673
T3
1
#
Unit
0 … n
xxx
End identification
1
CR
•
T1: "=" (1 character)
•
DCS no.: No. of the PC/DCS output as 3-digit decimal number
•
T2: "#" (1 character)
•
Value: Numerical value of the PC/DCS output or with interferred
measured value the text "FAULT"
Formatting of the value:
Character
Meaning
1
"- ": Minus with negative numbers
" ": Space with positive numbers
2 … 7
6-digit number after the decimal point
•
T3: "#" (1 character)
•
Unit: Unit as text (0 … n unit)
•
End identification: Carriage Return CR (1 sign)
Total length of the telegram: 14 characters+Unit character
Enquiry:
?001
Answer:
=001# 000673#%
? Block enquiry
All assigned PC/DCS values in the instrument are delivered as reply
to the block enquiry. The measured value is transmitted with six deci-
mal places without decimal point and with unit.
Number of bytes
Character
Identifier
1
?
End identification
1
CR
•
Identifier: "?" (1 character)
•
End identification: Carriage Return CR (1 sign)
Total length of the telegram: 2 characters
Reply from the signal
conditioning instrument
Example:
Enquiry of the control
system