VEGA Modbus-TCP, ASCII protocol User Manual

Page 22

background image

22

2 ASCII protocol

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

"N"-times repetition of the following telegram

(N=total number of assigned PC/DCS outputs)

Number of bytes

Character

T1

1

=

DCS no.

3

001 … 030

T2

1

#

Value

7

-000673

T3

1

#

Unit

0 … n

xxx

End identification

1

CR

T1: "=" (1 character)

DCS no.: No. of the PC/DCS output as 3-digit decimal number

T2: "#" (1 character)

Value: Numerical value of the PC/DCS output or with interferred

measured value the text "FAULT"

Formatting of the value:

Character

Meaning

1

"- ": Minus with negative numbers
" ": Space with positive numbers

2 … 7

6-digit number after the decimal point

T3: "#" (1 character)

Unit: Unit as text (0 … n unit)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: N*(14 characters+Unit character)
Enquiry:

?
Answer:

=001# 000673#kg

=002# 008246#%

=003#-000673#m

=004#-000673#m

? Block enquiry with length

The range stated in the enquiry with PC/DCS values is delivered as

reply to the range enquiry. The measured value is transmitted with six

decimal places without decimal point and with unit.

Number of bytes

Character

Identifier

1

?

Begin

1 … 3

001 … 030 or 1 … 30

Separator

1

L or I

Quantity

1 … 3

001 … 030 or 1 … 30

Reply from the signal

conditioning instrument

Example:

Enquiry of the control

system