Linearization Type
-
Possible types of linearization are: linear, user defined, cylindrical lying container, spherical
container
l
curve_points_1_10
-
X and Y values for the user defined linearization curve
l
curve_points_11_20
-
X and Y values for the user defined linearization curve
l
curve_points_21_30
-
X and Y values for the user defined linearization curve
l
curve_points_31_33
-
X and Y values for the user defined linearization curve
l
curve status
-
Result of table plausibility check
l
SUB_DEVICE_NUMBER
l
SENSOR_ELEMENT_TYPE
l
display_source_selector
-
Selects the type of value, which is displayed on the indication and adjustment module
l
max_peak_sensor_value
-
Holds the maximum sensor value. Write access resets to current value. Unit derives from
'S
ensor_range.unit'
l
min_peak_sensor_value
-
Holds the minimum sensor value. Write access resets to current value. Unit derives from
'S
ensor_range.unit'
l
Calibration Highest Point
-
Min./max.-adjustment: Upper calibrated point of the sensor. It refers to 'Cal_level_hi'. The unit is
defined in 'Sensor_range.unit'
l
Calibration Lowest Point
-
Min./max.-adjustment: Lower calibrated point of the sensor. It refers to 'Cal_level_lo'. The unit is
defined in 'Sensor_range.unit'
l
cal_level_hi
-
Min./max-adjustment: Level at 'Cal_point_hi'. When writing 'Cal_level_hi' and 'Cal_type' = 1
(Online) the 'Cal_point_hi' is automatically set to the current sensor value. The unit is defined in
'L
evel_unit'
l
cal_level_lo
-
Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_type' = 1
(Online), the 'Cal_point_lo' is automatically set to the current sensor value. The unit is defined in
'L
evel_unit'
l
cal_type
-
Min./max.-adjustment: Defines type of calibration: Dry: no influence of sensor value. Online:
current sensor value determines 'Cal_point_hi/lo'
l
level
-
Value after min./max.-adjustment
l
level_unit
-
Unit code of 'Level', 'Level_offset', 'Cal_level_hi', 'Cal_level_lo'
58