3 exchanging the electronics module – VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual
Page 45

Error
Cause
Rectification
Instrument does
not appear during
connection setup
Profibus DP cab-
le pole-reversed
Check cable and correct, if necessary
Incorrect termina-
tion
Check termination at the beginning
and end points of the bus and termin-
ate, if necessary, according to the
specification
Instrument not
connected to the
segment
Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
?
E
013
l
no measured value available
à Sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or
wrong parameter adjustment
?
E
017
l
Adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E
036
l
no operable sensor software
à Carry out a software update or send instrument for repair
?
E
041, E042, E043
l
Hardware error, electronics defective
à Exchange the instrument or send it in for repair
?
E
113
l
Communication conflict
à Exchange the instrument or send it in for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Set up" may have to be carried out again.
8
.3 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
Error messages via the
indicating and adjust-
ment module
Reaction after fault rec-
tification
VEGAPULS
63 • Foundation Fieldbus
45