beautypg.com

VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 50

background image

Input variable

Measured variable

distance between process fitting and product sur-
face

min. distance from flange

50 mm (1.97 in)

Measuring range depending on process fitting

-

Tri-Clamp 2", 3"

up to 10 m (32.81 ft)

-

bolting DN 50, DN 80

up to 10 m (32.81 ft)

-

flange DN 50, ANSI 2"

up to 10 m (32.81 ft)

-

Flange DN 80 … DN 150, Clamp 4",
ANSI

3" … 6"

up to 20 m (65.62 ft)

Reference conditions to measuring accuracy (according to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+18

… +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Other reference conditions

-

Reflector

ideal reflector, e.g. metal plate 2 x 2 m

-

False reflections

Largest false echo 20 dB smaller than the useful
echo

Characteristics and performance data

Frequency

K-band (26 GHz technology)

Meas. interval approx.

1 s

Beam angle -3 dB

5)

-

Tri-Clamp 2"

18°

-

Clamp 3", 4"

10°

-

Bolting DN 50

18°

-

Bolting DN 80

10°

-

flange DN 50, ANSI 2"

18°

-

Flange DN 80 … DN 150, ANSI 3" … 6"

10°

Step response or adjustment time

6)

< 1

s (dependent on the parameter settings)

Max. level change

Adjustable up to 1 m/min. (dependent on the
parameter settings)

Max. emitted HF power of the antenna system

-

Pulse peak power

< 2

mW

-

Pulse duration

< 2

ns

5)

Corresponds to the range with 50 % of the emitted power

6)

Time to output the correct level (with max. 10 % deviation) after a sudden
level change.

50

VEGAPULS

63 • Foundation Fieldbus

10 Annex

28451

-EN

-120530