3 Product description

VEGAMET 625 • Double channel HART

28970-EN-130701

The order data and the documentation of the instrument can be

retrieved by means of the instrument serial number on the type label.

To do this, go to www.vega.com, "VEGA Tools" and "serial number

search".

3.2 Principle of operation

VEGAMET 625 is a universal signal conditioning instrument for a

number of applications such as level, gauge, interface and process

pressure measurement. At the same time, it can serve as power

supply unit for connected sensors. VEGAMET 625 is designed for

connection of two independent VEGA HART sensors. Hence two

independent measurements can be carried out. By means of a third

measurement loop, the difference between the two input values can

be calculated.
On instruments with one of the optional interfaces (RS232/Ethernet),

the measured values can be retrieved via modem or network and dis-

played by means of a web browser, Visual VEGA or WEB-VV. It is also

possible to send measured values and messages via e-mail. The use

of VEGAMET 625 is particularly suitable for stocktaking, VMI (Vendor

Managed Inventory) and remote enquiry.

The VEGAMET 625 signal conditioning instrument can power two

HART sensors and process their measured signals via the same

cable. The measured value transmission is carried out via a digital

bus system (HART Multidrop). The requested parameter is displayed

and also sent to the integrated current outputs for further processing.

Hence the measured signal can be transferred to a remote indication

or a superordinate control system. Three level relays for control of

pumps or other actuators are also integrated.

Wide-range power supply unit with 20 … 253 V AC/DC for world-wide

use.
Detailed information about the power supply can be found in chapter

"Technical data".

3.3 Adjustment

The instrument can be adjusted with the following adjustment media:

With integrated display and adjustment unit

an adjustment software according to FDT/DTM standard, e.g.

PACTware and a Windows PC

The entered parameters are generally saved in VEGAMET 625, when

used with PACTware and PC also optionally in the PC.
Information:

When using PACTware and the corresponding VEGA DTM, additional

settings can be carried out which are not possible or only partly pos-

sible with the integrated display and adjustment unit. When using an

adjustment software, you either need one of the integrated interfaces

(RS232/Ethernet) or the interface converter VEGACONNECT.

Application area

Functional principle

Voltage supply