6 Setup with the integrated display and adjustment unit
VEGAMET 625 • Double channel HART
28970-EN-130701
→
Select the menu item "Device settings" with [->] and confirm with
[OK].
Under the menu item "Device settings", you can select the requested
application. For all level, gauge and differential measurements, the
application "Standard" is correct.
If an interface measurement should be carried out with a VEGAFLEX
67, you have to choose the menu item "Interface measurement" as
application. After the configuration of the inputs, the exact dielectric
figure for the upper medium must be entered. For further information
see chapter "Application examples".
→
Select the requested application with [->] and save your setting
with [OK]. Finally change to the menu item "Input" with [->].
Because VEGAMET 625 has two inputs, the measurement loops
must be assigned to the inputs. After the addresses of the HART sen-
sors are assigned, a list of the existing sensors can be prepared and
displayed via "Sensor selection - Sensor search". Now you can assign
the requested sensor to each measurement loop.
For transmission, VEGAMET 625 must be informed which "Sensor
value" should be used for further processing. Depending on the sen-
sor type this can be distance, pressure, interface or temperature. You
will find further information under the menu item "Meas. loop - Input".
→
Allocate the requested inputs to the appropriate measurement
loops, select the suitable sensor value and save your settings with
[OK]. After the first setup, you can modify the inputs also under
"Meas. loop - Input".
You can assign an unambiguous name to VEGAMET 625 via the
Device-TAG. This function is recommended when several instruments
are implemented and a good documentation of larger systems is
required.
→
Enter the requested values via the appropriate keys and save
your settings with [OK].
For instruments with integrated Ethernet interface, the automatic
addressing via DHCP is preset, i.e. the IP address must be assigned
by a DHCP server. Generally the instrument is contacted via the Host
Device settings - Applica-
tion
Device settings - Input
Device settings - Device-
TAG
Device settings - Host
Name/IP addr.