VEGAMET 625 • Double channel HART
28970-EN-130701
Min. programmable switching hysteresis 0.1 %
Ʋ Fault signal (switch over)
Switching condition off; unchanged
Mode pulse output
Ʋ Pulse length
350 ms
Current outputs
Quantity
3 x outputs
Function
Current output for level or flow/sampling pulse
Range
0/4 … 20 mA, 20 … 0/4 mA
Resolution
1 µA
Max. load
500 Ω
Fault signal (switch over)
0; 3,6; 4; 20; 20.5; 22 mA, unchanged
Accuracy
±20 µA (0.1 % of 20 mA)
Temperature error relating to 20 mA
0.005 %/K
Mode pulse output
Ʋ Voltage pulse
12 V DC at 20 mA with load 600 Ω
Ʋ Pulse length
200 ms
Ethernet interface (optional)
Quantity
1 x, cannot be combined with RS232
Data transmission
10/100 MBit
Plug connection
RJ45
Max. cable length
100 m (3937 in)
RS232 interface (optional)
Quantity
1 x, cannot be combined with Ethernet
Plug connection
RJ45 (modem connection cable on 9-pole D-SUB in the
scope of delivery)
Max. cable length
15 m (590 in)
Indications
Measured value indication
Ʋ graphic-capable LC display
(50 x 25 mm), with lighting
digital and quasianalogue indication
Ʋ Max. indicating range
-99999 … 99999
LED displays
Ʋ Status operating voltage
1 x LED green
Ʋ Status fault signal
1 x LED red
Ʋ Status operating relay 1/2/3
3 x LED yellow
Ʋ Status interface
1 x LED green
Adjustment
Adjustment elements
4 x keys for menu adjustment
PC adjustment
PACTware with respective DTM