VEGA VEGAMET 625 User Manual
Page 25
25
6 Setup with the integrated display and adjustment unit
VEGAMET 625 • Double channel HART
28970-EN-130701
→
Enter the requested parameters via the appropriate keys and
save your settings with [OK].
In the menu item "Display - Indication value", you can set the re-
quested indication value. The following options are available:
•
Percent: adjusted measured value without taking a probably
stored linearization into account
•
Lin. percent: adjusted measured value by taking a probably
stored linearization into account
•
Scaled: adjusted measured value by taking a probably stored
linarization into account as well as the values entered under "Scal-
ing"
•
Sensor value: input value delivered by the sensor. Presentation in
the selected adjustment unit
→
Enter the requested parameters via the appropriate keys and
save your settings with [OK].
When the instrument displays a failure message, further information is
available under the menu item "Diagnosis - Device status".
The simulation of a measured value is used to check the outputs and
connected components. The simulation can be applied to the percent-
age value, the lin. percentage value and the sensor value.
Note:
Please note that connected system parts (valves, pumps, motors,
control systems) are influenced by the simulation, thus unintentional
plant operating conditions can occur. The simulation is terminated
automatically after approxminately 10 minutes.
Display
Diagnostics
Service - Simulation