VEGA VEGASON 61 Foundation Fieldbus User Manual
Page 30

30
6 Set up with the display and adjustment module PLICSCOM
VEGASON 61 • Foundation Fieldbus
28790-EN-130417
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:
•
Measured value presentation
•
Adjustment
•
Medium
•
Vessel form
•
Damping
•
Linearization curve
•
Sensor-TAG
•
Displayed value
•
Unit of measurement
•
Language
The following safety-relevant data are not read out or written:
•
PIN
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the follow-
ing menu items to the reset values (see chart):
3)
Function
Reset value
Max. adjustment
0 m(d)
Min. adjustment
Meas. range end in m(d)
4)
Medium
Liquid
Vessel form
not known
Damping
0 s
Linearization
Linear
Sensor-TAG
Sensor
Displayed value
AI-Out
Unit of measurement
m(d)
The values of the following menu items are not reset to the reset
values (see chart) with "Reset":
Function
Reset value
Language
No reset
Default setting
Like basic adjustment, but in addition, special parameters are reset to
default values.
5)
Copy sensor data
Reset
3)
Sensor-specific basic adjustment.
4)
Depending on the sensor type, see chapter "Technical data".