Options, Correction in the point - ε – VEGA VEGALOG 571 User Manual
Page 24
24
VEGALOG 571
100 %
0
0
40
100 %
40
Options
Correction in the point
-
ε
r
-correction
- only in conjunction with
capacitive electrodes
- steepness correction of
the adjustment character-
istics
Product description
Correction in the point
Zero point correction
0
100 %
100 %
0
corrected measured value, e.g. 0 %
Measured value too low
incorrect course of measured values
incorrect course of measured values
Dielectric constant too big,
measured value too high
Dielectric constant too small,
measured value too low
Measured value too high
actual measured value in %
actual measured value in %
corrected measured value, e.g. 40 %
Real value correction
Density correction
incorrect course of measured values
incorrect course of measured values
higher density,
measured value too high
lower density,
measured value too low
100 %
40
0
40
0
100 %
20
0
20
100 %
0
100 %
Measured value too low
Measured value too high
actual measured value in %
actual measured value in %
corrected measured value, e.g. 20 %
corrected measured value, e.g. 40 %
Zero point correction
- with unpressurised sensor
- parallel shifting of the
adjustment characteristics
Real value correction
- with given %-value
- parallel shifting of the
adjustment characteristics
Density correction
- only in conjunction with
hydrostatic pressure
transmitters
- steepness correction of
the adjustment character-
istics
Further options are tare
function and monitoring func-
tion.