Dometic MCS15 User Manual
Page 22
EN
Programming
MCS5, MCS15
22
P-17: Reset Memorized Defaults
The default programming parameters can be reset as follows:
➤ Select “rSt”.
✓ This restores the programmable parameters to the default values.
The default parameters listed in the “Programmable Parameters Table” on
page 16 may be altered by the installing dealer or end user. Once new de-
faults are entered and memorized the factory defaults will be overwritten. The
original factory program parameters as listed in the table may be restored
manually.
P-18, P-19: Reserved for Future Option
P-20: Filter Threshold
This feature is to remind you to change the air filter on a unit. The units are
x10 hours.
By default it is off, which is designated with a “00”, but it can be set between
100 and 2500 hours. After the unit has reached its threshold time, it will dis-
play a “FIL” remind 1 s every 10 s.
P-21: Current Filter Time
This feature is used to display the amount of time the current filter has been
on the unit. The units are x10 hours.
➤ In order to reset this parameter, simply press the Up or Down Button.
P-22: Voltage Calibration
This feature displays the voltage reading as seen by the display. Calibrating
this parameter will provide a more accurate voltage when calculating low
voltage for P-7. It will display a live reading of the voltage.
➤ Manipulate the reading by pressing the Up or Down Button.