EN

Programming

MCS5, MCS15

16

8.6

Restore Memorized Default Settings

The memorized default settings can be restored as follows.

➤ Enter the Program Mode.
➤ Set P-17 to “rSt”.
➤ Exit the Program Mode.
✓ The software version number (e.g. “A12”) appears in the display.
✓ The memorized default settings are restored and the Marine Climate Sys-

tem returns to the Off Mode.

8.7

Programmable Parameters

Programmable Parameters Table

Program

number

Description

Default Range

P-1

Operating Mode

0

0 = Automatic mode
1 = Cool only mode
2 = Heat only mode

P-2

High Fan Speed Limit
(arbitrary units)

95

65 – 95

P-3

Low Fan Speed Limit
(arbitrary units)

55

30 – 64

P-4

Compressor Staging
Time Delay

15

5 – 135 s

P-5

Temperature Sensor
Calibration

Ambient

Temperature

Ambient 10 °F

P-6

Failsafe

3

0 = Minimum protection
1 = Continuous, no display
2 = Continuous, with display
3 = Four failures, reset required

P-7

Low AC Voltage Shut-
down (Volts)

115 V – OFF

220/230 V – OFF

75 – 105
175 – 205

P-8

De-Icing Cycle

1

OFF
1
= On with 5 °F faceplate sensor
differential
2 = On with 7 °F faceplate sensor
differential

P-9

High Water Tempera-
ture Limit (°F)

OFF

100 – 150