DeviceNet Network Scanner DVPDNET-SL
DVP-PLC Operation Manual
26
editing area to 0.
When M1 = On, DVPDNET-SL will send out request message. Write 0004Hex into Class 99 >>
Instance 1 >> Attribue 2 of the target equipment (node address: 02). If the communication of
explicit message is successful, the slave will return with a response message.
When M1 = On, DVPDNET-SL will only send out request message once. If you would like it to
send out request message again, you will have to change ReqID.
When the writing is successfully done, the message responded from the target equipment will be
stored in D6000 ~ D6003.
7 Bit-Strobe
Command
7.1 Principle
of
Bit-Strobe
Bit-strobe is one of the standard I/O transmission methors for DeviceNet. The length of command is fixed to
8 bytes (i.e. 64 bits), and every bit corresponds to a slave.
Corresponding nodes on the network
PLC
device
b15
b14
b13
…
b1
b0
D6282
Node 15
Node 14
Node 13
…
Node 1
Node 0
D6283
Node 31
Node 30
Node 29
…
Node 17
Node 16
D6284
Node 47
Node 46
Node 45
…
Node 33
Node 32
D6285
Node 63
Node 62
Node 61
…
Node 49
Node 48
When b0 of D6282 = 0, the node 0 equipment will be selected, and it will need to respond with a message to
the master. When b0 and b1 of D6282 = 0, the node 0 and node 1 equipment will be selected, and they will beed
to respond with a message to the master.
b0
b1
b17
b15 b14
b30
b2
b18
b16
b31
D6283
Node 0
Node 1
Node 2
Node 14
D6282
In the bit-strobe mode, the master will not send control data to the slave node. However, when its
corresponding bit is set to 0, the slave node will have to respond with I/O data to the master. When its
corresponding bit is set to 1, the slave node will not have to respond with I/O data to the master.
8
Display of Node Status on Network
8.1
Display of Node Status in Scan List
DVPDNET-SL does read-time monitoring to the nodes in the scan list and maps the status of every node to a
bit. You can acquire the node status by monitoring D6032 ~ D6035. See the table below for the corresponding
relation between PLC devices and the nodes on the network: