Devicenet network scanner dvpdnet-sl – 2nd Ave. DVPDNET-SL DeviceNet Network Scanner DVP-0204520-02 User Manual
Page 25
DeviceNet Network Scanner DVPDNET-SL
DVP-PLC Operation Manual
23
Compulsory settings in IFD9502
Parameter
Set value
Explanation
Node address
02
Set the node address of IFD9502 to “02".
Baud rate
500kbps
Set the communication speed of IFD9502 and bus to
“500kbps”.
Compulsory settings in VFD-B
Parameter
Set value
Explanation
02-00
04
The main frequency is operated on RS-485 interface.
02-01 03
The operation commands are operated on the communication
interface. Operation by keys is valid.
09-00
01
Communication address of VFD-B: 01
09-01
03
Baud rate: 38,400
09-04
03
Modbus RTU mode. Data format <8, N, 2>
Explanations on devices
Explanation
PLC device
Content
15 14 13 12 11 10 9
8 7 6 5 4
3
2
1
0
D6250
0101Hex
ReqID = 01Hex
Command = 01Hex
D6251
0005Hex
Port = 00Hex
Size = 05Hex
D6252 0E02Hex
Service Code = 0EHex
MAC ID = 02Hex
D6253
0001Hex
High bye of Class ID =00Hex Low byte of Class ID = 01Hex
D6254
0001Hex
High byte of Instance ID =
00Hex
Low byte of Instance ID =
01Hex
Request
message
editing area
D6255
0001Hex
N/A
Attribute ID = 01Hex
D6000
0101Hex
ReqID = 01Hex
Status = 01Hex
D6001
0002Hex
Port = 00Hex
Size = 02Hex
D6002 8E02Hex
Service Code = 8EHex
MAC ID = 02Hex
Response
message
editing area
D6003 031FHex
High byte of Service Data =
03Hex
Low byte of Service Data =
1FHex
(3) PLC
program
MOV
H0101
D6250
M1002
ZRST
D6250
D6281
M0
MOV
H0005
D6251
MOV
H0E02
D6252
MOV
H0100
D6253
MOV
H0100
D6254
MOV
H0100
D6255
ZRST
D6000
D6031
Reset response message editing area
& request message editing area
ReqID = 01, Command = 01
Port = 00, Size = 05
Service Code = 0E, MAC ID = 02
Class ID to be read = 01
Instance ID to be read = 01
Attribute ID to be read = 01