Devicenet network scanner dvpdnet-sl – 2nd Ave. DVPDNET-SL DeviceNet Network Scanner DVP-0204520-02 User Manual
Page 27

DeviceNet Network Scanner DVPDNET-SL
DVP-PLC Operation Manual
25
Parameter
Set value
Explanation
02-01 03
The operation commands are operated on the communication
interface. Operation by keys is valid.
09-00
01
Communication address of VFD-B: 01
09-01
03
Baud rate: 38,400
09-04
03
Modbus RTU mode. Data format <8, N, 2>
Explanations on devices
Explanation
PLC device
Content
15 14 13 12 11 10 9
8 7 6 5 4
3
2
1
0
D6250
0101Hex
ReqID = 01Hex
Command = 01Hex
D6251
0005Hex
Port = 00Hex
Size = 07Hex
D6252 0E02Hex
Service Code = 10Hex
MAC ID = 02Hex
D6253
0099Hex
High byte of Class ID = 00Hex Low byte of Class ID = 99Hex
D6254
0001Hex
High byte of Instance ID =
00Hex
Low byte of Instance ID =
01Hex
D6255
0002Hex
N/A
Attribute ID = 02Hex
Request
message
editing area
D6256
0004Hex
High byte of data = 00Hex
Low byte of data = 04Hex
D6000
0101Hex
ReqID = 01Hex
Status = 01Hex
D6001
0002Hex
Port = 00Hex
Size = 02Hex
D6002
9002Hex
Service Code = 90EHex
MAC ID = 02Hex
Response
message
editing area
D6003
0004Hex
High byte of Service Data =
00Hex
Low byte of Service Data =
04Hex
(3) PLC
program
MOV
H0101
D6250
M1002
ZRST
D6250
D6281
M1
MOV
H0008
D6251
MOV
H0E02
D6252
MOV
H0099
D6253
MOV
H0001
D6254
MOV
H0002
D6255
ZRST
D6000
D6031
Reset response message editing area
& request message editing area
ReqID = 01, Command = 01
Port = 00, Size = 08
Service Code = 0E, MAC ID = 02
Class ID to be write= 99
Instance ID to be
= 01
written
Attribute ID to be
= 02
written
MOV
H0004
D6256
Data to be written = 0004
(4) Program
explanations
In the beginning of the program, clear the response message editing area and request message