York E*BD-(T User Manual
Page 25
246819-BTG-H-0208
Unitary Products Group
25
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
EABD-F018S
EVAPORATOR COIL MODEL NO
FC/MC/PC/UC18
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
450
600
750
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
20.9
1.5
4.1
21.7
0.7
8.8
22.5
1.4
4.6
70
19.9
1.5
3.8
20.7
1.1
6.3
21.6
1.5
4.3
80
18.8
1.6
3.5
19.7
1.6
3.7
20.6
1.5
4.0
47
60
17.4
1.3
3.8
18.4
1.3
4.1
19.3
1.3
4.4
70
16.3
1.4
3.5
17.3
1.0
5.6
18.3
1.3
4.1
80
15.2
1.4
3.1
16.3
0.7
7.0
17.3
1.4
3.7
40
60
15.5
1.3
3.6
16.4
1.2
3.9
17.3
1.2
4.2
70
14.5
1.3
3.2
15.3
1.3
3.5
16.0
1.3
3.8
80
13.4
1.3
2.9
14.1
1.3
3.1
14.8
1.3
3.3
30
60
13.2
1.2
3.2
13.8
1.2
3.4
14.3
1.2
3.6
70
12.1
1.2
2.9
12.7
1.2
3.1
13.4
1.2
3.3
80
10.9
1.3
2.5
11.7
1.2
2.8
12.5
1.2
3.0
17
60
9.6
1.1
2.5
10.0
1.1
2.6
10.4
1.1
2.8
70
8.7
1.2
2.2
9.0
1.1
2.3
9.3
1.1
2.4
80
7.8
1.2
1.9
8.0
1.2
2.0
8.2
1.2
2.1
10
60
8.4
1.2
2.1
8.9
1.1
2.3
9.5
1.1
2.5
70
7.5
1.2
1.9
8.0
1.1
2.1
8.5
1.1
2.2
80
6.5
1.2
1.6
7.0
1.2
1.8
7.5
1.1
1.9
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
MA08B
FC/MC18B
1.00
1.00
1.00
AHP18
–
1.00
0.99
0.98
F*FP024
–
0.99
0.99
0.98
MV12B
FC/MC18B
0.97
0.94
0.91
AV24
–
0.97
0.94
0.91
–
HC18
0.99
1.01
1.00
Variable Speed
Furnace *
Coil
T.C.
S.C.
KW
(F,L)L8VA12
FC/MC/PC18A
0.97
0.93
0.91
FL9VA12
FC/MC/PC18A
0.98
0.95
0.93
FL9(C,V)B12
FC/MC/PC18B
0.97
0.94
0.91
(F,L)L8VA12
HC18
0.98
0.95
0.93
FL9VA12
HC18
0.97
0.93
0.91