York E*BD-(T User Manual
Page 24
246819-BTG-H-0208
24
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
*
= Single-phase outdoor units only.
*
= Single-phase outdoor units only.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
EABD-F060S, EABD-(T,W)060S**
INDOOR COIL MODEL NO.
FC/MC/PC/UC60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1600
1800
2000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
47.8
51.8
54.4
58.7
65.2
49.3
52.9
55.5
60.2
66.6
50.8
54.1
56.6
61.7
68.0
S.C.
47.8
47.1
41.0
40.0
31.0
49.3
50.2
44.0
43.0
32.6
50.8
53.4
46.9
46.0
34.3
K.W.
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
3.0
2.9
2.9
2.9
2.9
3.0
75
T.C.
47.0
50.3
52.6
57.1
63.0
48.7
51.4
53.7
58.5
64.3
50.4
52.5
54.8
59.8
65.6
S.C.
47.0
46.5
40.2
39.4
30.6
48.7
49.6
43.2
42.4
32.3
50.4
52.5
46.1
45.3
33.9
K.W.
3.3
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.3
3.4
85
T.C.
46.1
48.8
50.8
55.6
60.9
48.1
49.8
51.8
56.7
62.1
50.0
50.8
52.9
57.9
63.3
S.C.
46.1
45.9
39.4
38.9
30.3
48.1
49.0
42.4
41.7
31.9
50.0
50.8
45.3
44.6
33.6
K.W.
3.7
3.7
3.7
3.7
3.8
3.7
3.7
3.7
3.8
3.8
3.7
3.7
3.7
3.8
3.8
95
T.C.
45.3
47.3
48.9
54.0
58.7
47.4
48.2
50.0
55.0
59.8
49.6
49.1
51.1
55.9
60.9
S.C.
45.3
45.2
38.6
38.3
29.9
47.4
48.2
41.6
41.1
31.6
49.6
49.1
44.6
43.9
33.2
K.W.
4.1
4.1
4.1
4.2
4.2
4.1
4.1
4.1
4.2
4.2
4.1
4.2
4.1
4.2
4.2
105
T.C.
43.1
44.3
45.5
50.3
55.9
45.1
45.2
46.4
51.2
56.9
47.1
46.1
47.3
52.0
57.9
S.C.
43.1
43.1
36.8
36.5
28.6
45.1
45.2
39.5
39.2
30.3
47.1
46.1
42.3
42.0
31.9
K.W.
4.6
4.7
4.7
4.7
4.8
4.7
4.7
4.7
4.7
4.8
4.7
4.7
4.7
4.8
4.8
115
T.C.
40.9
41.4
42.3
46.8
53.1
42.8
42.3
43.0
47.5
54.0
44.7
43.2
43.7
48.2
55.0
S.C.
40.9
41.1
35.0
34.8
27.3
42.8
42.3
37.6
37.4
29.0
44.7
43.2
40.2
40.1
30.7
K.W.
5.2
5.3
5.2
5.3
5.4
5.2
5.3
5.3
5.3
5.4
5.2
5.3
5.3
5.3
5.4
125
T.C.
38.8
38.6
39.0
43.2
50.3
40.6
39.4
39.5
43.8
51.2
42.3
40.2
40.0
44.4
52.1
S.C.
38.8
38.6
33.2
33.1
26.0
40.6
39.4
35.6
35.7
27.7
42.3
40.2
38.0
38.2
29.4
K.W.
5.7
5.8
5.8
5.9
5.9
5.8
5.8
5.8
5.9
6.0
5.8
5.9
5.8
5.9
6.0
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
**
For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.
Air Handler
Coil
T.C.
S.C.
KW
MA20D
FC/MC60D
1.00
1.00
1.00
MA20D
MC61D
1.01
1.01
1.01
AHP/SHP60
–
1.00
0.98
1.00
F*FV060*
–
0.98
0.98
0.98
MV20D*
FC/MC60D
0.98
0.98
0.98
MV20D*
MC61D
1.00
0.98
1.00
AV/SV60*
–
1.00
0.98
1.00
–
HC60
0.99
0.98
0.99
–
HD60
0.98
0.98
0.98
–
MC61
1.01
1.01
1.01
Variable Speed
Furnace *
Coil
T.C.
S.C.
KW
FL9(C,V)D20
FC/MC/PC60D
0.99
0.95
0.99
(F,L)L8VC20
FC/PC60C
0.99
0.95
0.99
FL9(C,V)C20
FC/PC60C
0.98
0.97
0.98
FL9(C,V)D20
HC60
0.99
0.95
0.99
(F,L)L8VC20
HD60
0.99
0.94
0.99
FL9(C,V)D20
HD60
0.99
0.94
0.99
FL9(C,V)D20
MC61D
0.98
0.96
0.98