York E*BD-(T User Manual
Page 2

246819-BTG-H-0208
2
Unitary Products Group
All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.
Physical and Electrical Data
-
1 Phase
MODEL
EABD-F018S EABD-F024S EABD-F030S EABD-F036S EABD-F042S EABD-F048S EABD-F060S
Unit Supply Voltage
208-230V, 1
φ, 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity
9.9
15.0
16.9
19.8
25.0
32.7
37.8
Max. Overcurrent Device Amps
2
15
25
25
30
40
50
60
Min. Overcurrent Device Amps
3
15
20
20
20
30
35
40
Compressor Type
4
Recip
Recip
Recip
Recip
Recip
Scroll
D
Scroll
D
Compressor
Amps
Rated Load
7.5
10.7
12.4
14.6
18.8
25.0
29.1
Locked Rotor
41
44
60
78
78
115
150
Crankcase Heater
Yes
Yes
Yes
Yes
Yes
No
No
Fan Motor Amps Rated Load
0.5
1.5
1.5
1.5
1.5
1.5
1.5
Fan Diameter Inches
22
22
22
22
22
24
24
Fan Motor
Rated HP
1/15
1/4
1/4
1/4
1/4
1/4
1/4
Nominal RPM
850
850
850
850
850
850
850
Nominal CFM
2,000
3,250
3,450
3,500
3,500
3,400
3,500
Coil
Face Area Sq. Ft.
15.72
18.34
20.96
23.58
23.58
24.00
27.00
Rows Deep
1
1
1
1
1
2
2
Fin / Inches
22
22
22
22
22
18
18
Liquid Line Set OD (Field Installed)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line Set OD (Field Installed)
3/4
3/4
7/8
7/8
7/8
7/8
1-1/8
Unit Charge (Lbs. - Oz.)
5
7 - 1
6 - 6
8 - 7
8 - 7
8 - 7
12 - 8
16 - 7
Charge Per Foot, Oz.
0.68
0.68
0.70
0.70
0.70
0.70
0.76
Operating Weight Lbs.
172
184
196
208
208
250
294
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
5. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
A
B
C
Unit
Model
Dimensions
(Inches)
Refrigerant
Connection
Service Valve Size
A
1
1. Including Fan Guard.
* Adapter fitting required for 1-1/8” line set.
B
C
Liquid
Vapor
018
27
37
27
3/8”
3/4”
024
31
37
27
030
35
37
27
7/8”
036
39
37
27
042
39
37
27
048
34
43
32
060
38
43
32
7/8”*