Table 37: unit clearances, Detail a, Detail b – York PREDATOR DR090 User Manual

Page 44: Detail c

background image

246721-YTG-C-0606

44

Unitary Products Group

FIGURE 19 - DR150 UNIT DIMENSIONS

11-1/2

89

27

59

50-3/4

30-11/32

4-1/4

6-3/16

17-3/16

24-3/16

30-3/16

119-7/16

Convenience

Outlet

Convenience
Outlet Power

Entry 7/8

For Gas Pipe Entry

see DETAIL A

For Baserail

Dimensions

see

DETAIL B

FRONT

LEFT

Power

Entry

2-1/2

Control

Entry

7/8

For Drain Dimensions

see DETAIL C

TABLE 37: UNIT CLEARANCES

Top

1

1.

Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.

72”

Right

12”

Front

36”

Left

36”

Rear

2

2.

To remove the slide-out drain pan, a rear clearance of 60” is
required. If space is unavailable, the drain pan can be
removed through the front by separating the corner wall.

36”

Bottom

3

3.

Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.

0”

5 - 1 / 4

B a s e

P a n

1 7 - 1 3 / 1 6

V i e w o f W a l l A c r o s s f r o m C o i l

G a s P i p e I n l e t

DETAIL A

3-3/4

3-9/16

2-3/8

DETAIL B

5 - 3 / 8

DETAIL C