York SPLIT-SYSTEM YHJD18 THRU 60 User Manual
Page 22

398612-YTG-B-0608
22
Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO.
YHJD60S21S1
INDOOR COIL MODEL NO.
FC/MC62
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1600
1800
2000
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
54.0
55.2
55.2
60.7
64.4
56.4
57.0
56.5
62.3
65.6
58.7
58.7
57.7
63.9
66.7
S.C.
49.8
47.0
36.8
39.6
29.4
52.1
50.2
40.6
42.1
30.8
54.4
53.5
44.3
44.6
32.2
KW
2.9
2.9
3.0
3.0
3.1
3.0
2.9
3.0
3.0
3.1
3.0
2.9
3.0
3.0
3.1
75
T.C.
52.5
53.5
52.6
58.5
61.5
54.7
55.3
53.9
60.0
62.9
57.0
57.1
55.2
61.5
64.2
S.C.
48.2
45.9
36.6
38.4
28.4
50.4
49.1
39.9
41.0
30.0
52.6
52.2
43.3
43.5
31.6
KW
3.3
3.4
3.4
3.4
3.5
3.4
3.4
3.4
3.5
3.5
3.4
3.4
3.4
3.5
3.5
85
T.C.
50.9
51.8
50.1
56.2
58.7
53.0
53.7
51.4
57.6
60.2
55.2
55.5
52.7
59.1
61.7
S.C.
46.7
44.9
36.3
37.3
27.5
48.7
47.9
39.3
39.8
29.2
50.8
50.9
42.3
42.4
31.0
KW
3.7
3.8
3.8
3.9
3.9
3.8
3.8
3.8
3.9
4.0
3.8
3.8
3.9
3.9
4.0
95
T.C.
49.3
50.2
47.6
53.9
55.8
51.4
52.0
48.9
55.3
57.5
53.4
53.8
50.2
56.6
59.2
S.C.
45.1
43.9
36.0
36.1
26.6
47.1
46.8
38.7
38.7
28.5
49.0
49.6
41.3
41.2
30.4
KW
4.2
4.3
4.3
4.3
4.4
4.2
4.3
4.3
4.3
4.4
4.2
4.3
4.3
4.3
4.4
105
T.C.
46.9
47.7
44.9
51.1
52.9
49.0
49.3
46.2
52.3
54.3
51.0
50.9
47.5
53.6
55.8
S.C.
42.8
42.0
34.8
34.7
25.5
44.7
44.5
37.3
37.2
27.3
46.6
46.9
39.8
39.8
29.2
KW
4.8
4.9
4.9
4.9
5.0
4.8
4.9
4.9
4.9
5.0
4.8
4.9
4.9
5.0
5.0
115
T.C.
44.6
45.2
42.3
48.3
50.0
46.6
46.7
43.6
49.5
51.3
48.6
48.1
44.8
50.6
52.5
S.C.
40.7
40.2
33.5
33.3
24.5
42.4
42.2
35.9
35.8
26.2
44.2
44.2
38.3
38.3
28.0
KW
5.3
5.5
5.5
5.5
5.6
5.4
5.5
5.5
5.5
5.6
5.4
5.5
5.5
5.6
5.6
125
T.C.
42.3
42.8
39.7
45.6
47.2
44.2
44.0
40.9
46.6
48.2
46.2
45.3
42.2
47.6
49.3
S.C.
38.5
38.5
32.3
32.0
23.4
40.1
40.0
34.5
34.4
25.1
41.8
41.5
36.8
36.9
26.8
KW
5.9
6.0
6.1
6.1
6.2
6.0
6.1
6.1
6.1
6.2
6.0
6.1
6.1
6.2
6.2
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
MV20D
FC/MC62D
1.00 1.01 1.00
MA20D
FC/MC62D
1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
PV8*C20
FC/MC62D
1.00 1.00 1.00
P(C,V)9*C20
FC/MC62D
1.00 1.01 1.00
P(C,V)9*D20
FC/MC62D
0.98 1.01 0.98