York SPLIT-SYSTEM YHJD18 THRU 60 User Manual
Page 11

398612-YTG-B-0608
Johnson Controls Unitary Products
11
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by
the total electric power input during the same period.
— = Not Applicable.
13 SEER HP WITH AV / SV / F*FV - VARIABLE SPEED
YHJD18S21S1
AV24
–
17.0 3.46 1.40 9.0 2.32 1.08 8.00
YHJD24S21S1
AV24
–
22.0 4.04 1.62 12.0 2.64 1.28 8.40
YHJD30S21S1
AV36
–
28.0 3.80 2.18 14.0 2.38 1.76 8.00
YHJD36S21S1
AV36
–
33.0 3.74 2.61 20.0 2.62 2.23 8.80
AV/SV48
–
33.0 3.74 2.61 20.0 2.62 2.23 8.80
YHJD42S21S1
AV/SV48
–
40.0 3.68 3.18 24.0 2.74 2.58 8.85
AV/SV60
–
40.0 3.70 3.20 24.0 2.74 2.58 8.85
F4FV060
–
40.0 3.70 3.20 24.0 2.74 2.58 8.85
YHJD48S21S1
AV/SV48
–
48.0 3.50 3.97 37.0 2.82 3.84 8.00
AV/SV60
–
48.0 3.48 3.99 37.0 2.82 3.84 8.00
F4FV060
–
48.0 3.48 3.99 37.0 2.82 3.84 8.00
13 SEER HP WITH AHP / SHP / F*FP
YHJD18S21S1
AHP18
–
17.0 3.26 1.54 9.0 2.18 1.23 7.70
AHP24
–
17.0 3.28 1.52 9.0 2.18 1.22 7.70
F4FP024
–
17.0 3.26 1.54 9.0 2.18 1.23 7.70
YHJD24S21S1
AHP24
–
23.0 3.74 1.80 12.0 2.46 1.45 7.70
AHP30
–
23.0 3.74 1.80 12.0 2.44 1.46 7.70
F4FP030
–
23.0 3.74 1.80 12.0 2.46 1.45 7.70
YHJD30S21S1
AHP30
–
29.0 3.54 2.41 15.0 2.24 1.96 7.65
AHP36
–
29.0 3.54 2.41 15.0 2.24 1.96 7.65
F4FP040
–
29.0 3.54 2.41 15.0 2.24 1.96 7.65
YHJD36S21S1
AHP36
–
34.0 3.58 2.78 21.0 2.52 2.39 8.50
AHP42
–
34.0 3.60 2.76 20.0 2.52 2.37 8.55
AHP/SHP60
–
33.0 3.74 2.61 20.0 2.62 2.23 8.80
F4FP045
–
34.0 3.58 2.78 21.0 2.52 2.39 8.50
F5FP048
–
33.0 3.74 2.61 20.0 2.62 2.23 8.80
F5FP060
–
33.0 3.74 2.61 20.0 2.62 2.23 8.80
YHJD42S21S1
AHP/SHP48
–
42.0 3.56 3.41 25.0 2.64 2.75 8.60
AHP/SHP60
–
40.0 3.70 3.20 24.0 2.74 2.58 8.85
F4FP045
–
42.0 3.56 3.41 25.0 2.64 2.75 8.60
F5FP048
–
40.0 3.70 3.20 24.0 2.74 2.58 8.85
F5FP060
–
40.0 3.70 3.20 24.0 2.74 2.58 8.85
YHJD48S21S1
AHP/SHP48
–
48.0 3.40 4.13 37.0 2.74 3.99 7.70
AHP/SHP60
–
48.0 3.48 3.99 37.0 2.80 3.87 8.00
F5FP060
–
48.0 3.48 3.99 37.0 2.80 3.87 8.00
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and
no supplemental electric heat operation.
HEATING PERFORMANCE - With Air Handler (Continued)
UNIT
MODEL*
AIR
HANDLER
COIL
1
MODEL
ARI HEATING
2
47
°F
17
°F
HSPF
MBH
COP
KW
MBH
COP
KW
STD