beautypg.com

Accessories, Sound power ratings, Typical installation typical field wiring – York SPLIT-SYSTEM YHJD18 THRU 60 User Manual

Page 15

background image

398612-YTG-B-0608

Johnson Controls Unitary Products

15

ACCESSORIES

Refer to Price Manual for specific model numbers.

Start Assist Kit (2SA067*)

Blower Time Delay - Available to increase efficiency when
installed. Installs on indoor section and maintains blower for
approximately one minute after cooling thermostat has been
satisfied.

Hard Start Kits - Provides required starting torque for use
with Thermal Expansion Valve Kit.

Low Temperature Cutout (2LT06700224) - Prevents heat
pump operation below -1

0°F ambient temperature.

Compressor Blanket - Designed to further reduce the nor-
mal operating sound.

Add-on Fossil Fuel Control - Interface controls for use with
gas, oil furnaces and the heat pump system are available.

Thermal Expansion Valve Kit - 1TVM Series TXV kit used to
improve system performance.

Outdoor Thermostat (2TD06700124) - Provides additional
staging of supplemental electric heat.

Room Thermostats - A wide selection of matching thermo-
stats is available to provide features required for any installa-
tion.

2H/1C, manual changeover electronic non-programmable
thermostat.

3H/2C, non-programmable digital thermostat.

3H/2C, auto/manual changeover, electronic programmable,
7-day, hardwire thermostat.

* For the most current accessory information, refer to the
price book or consult factory.

SOUND POWER RATINGS

* Rated in accordance with ARI 270-95 Standards.

TYPICAL INSTALLATION

TYPICAL FIELD WIRING

UNIT MODEL

(dBA)*

Cooling

Heating

018

TBD

TBD

024

TBD

TBD

030

TBD

TBD

036

TBD

TBD

042

TBD

TBD

048

TBD

TBD

060

TBD

TBD

THERMOSTAT

SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT

TO INDOOR COIL

TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK

NEC CLASS 2 WIRING

NEC CLASS 1 WIRING

ALL OUTDOOR WIRING
MUST BE WEATHERPROOF.

CONTROL
ACCESS
PANEL

WEATHERPROOF
DISCONNECT
SWITCH

MINIMUM 18” SERVICE
ACCESS CLEARANCE
ON ONE SIDE

60” OVERHEAD
CLEARANCE

6” CLEARANCE
AROUND PERIMETER

NOTE:

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

POWER WIRING

208/230-1-60

CONTACTOR
TERMINALS

COIL

GND.

LUG

C

Y

R

G

W

Y

R

G

W

POWER WIRING
CONTROL WIRING
FACTORY WIRING

24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)

FURNACE OR AIR HANDLER TERMINAL BLOCK

ROOM THERMOSTAT

CONDENSING UNIT

ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.

TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.

*

*