5

MODEL

DEB

POWER SUP-

PLY

VOLTAGE

LIMITATIONS

1

COMPRESSOR

COND.

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

AMPS

2

MAX.

HACR

BREAKER

SIZE,

AMPS

UNIT

POWER

FACTOR

TRANSFORMER

SIZE (VA)

MIN.

MAX.

RLA

LRA

018

208/230-1-60

187

253

9.0

48.0

1.1

2.6

14.9

20

20

.96

40

024

208/230-1-60

187

253

11.5

60.0

1.1

2.6

18.1

25

25

.96

40

030

208/230-1-60

187

253

14.7

73.0

1.1

2.6

22.1

30

30

.96

40

036

208/230-1-60

187

253

17.3

94.0

1.1

3.5

26.2

35

35

.96

40

042

208/230-1-60

187

253

20.5

120.0

1.1

3.5

30.2

40

40

.96

40

048

208/230-1-60

187

253

24.4

140.0

1.3

4.0

35.8

45

45

.96

40

060

208/230-1-60

187

253

28.9

165.0

1.3

4.0

44.4

60

60

.96

40

= Rated in accordance with ARI Standard 110, utilization range “A”.

= Dual element, time delay type.

TABLE 4 -

ELECTRICAL DATA (BASIC UNIT)

*

= KW listed is for 240 volts, use this table for 208 or 230 volts.

ELECTRIC HEAT

CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE

KW CAP. MULTI-

PLIER

240

208
230

.75
.92