beautypg.com

York CHAMPION D2EB User Manual

Page 4

background image

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the current
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.
The unit must be electrically grounded in accordance with local
codes or, in their absence, with the N.E.C./C.E.C. Voltage toler-
ances which must be maintained at the compressor terminals
during starting and running conditions are indicated on the unit
Rating Plate and Table 3.

The wiring entering the cabinet must be provided with me-
chanical strain relief.

A fused or HACR breaker disconnect switch should be field pro-
vided for the unit. If any of the wire supplied with the unit must be
replaced, replacement wire must be of the type shown on the wir-
ing diagram.

Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate unit
wiring diagram for control circuit and power wiring information.

COMPRESSORS

Units are shipped with compressor mountings factory-adjusted
for shipping.

CAUTION: Loosen compressor mounting bolts

half turn before operating unit.

174065-YIM-A-0206

4

Unitary Products Group

FIG. 2 - TYPICAL FIELD WIRING DIAGRAM

POWER WIRING

4

/

9

4

/

+

;

;

9

+

24 VOLT TRANSFORMER

UNIT TERMINAL STRIP

THERMOSTAT

NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.25
AMPS FOR ALL MODELS.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can

cause improper and dangerous operation. Verify proper operation after servicing.

PROGRAMMABLE

THERMOSTAT ONLY

CONTROL WIRING

** = Minimum wire size of 18 AWG

wire should be used for all field
installed 24 volt wire.

**

*

* = Only required on units with

supplemental electric heat.

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE DISCON-

NECT SWITCH, WIRING &

OVERCURRENT PROTECTION.