York AHP18 User Manual

Page 10

background image

255029-YTG-M-0610

10

Johnson Controls Unitary Products

2. Heaters are 3 Phase.

COOLING MODELS WITH ELECTRIC HEAT WIRING

*

Optional dehumidification humidistat switch contacts open on humidity rise.

Notes:
1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second blower off delay for SEER
enhancement.
2. Move HUM STAT Jumper on AH Control Board to YES position if Humidistat is used.
3. MODE Jumper on AH control board should be set to A/C for air conditioners.

ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

Models

Heat Kit -

Three Phase

Heater

Amps

240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

1

Amps/Type

75°C Wire Size - AWG

208V

240V

208V

240V

208V

240V

AHP24B**H21

4HK06501025

23.1

27.1

31.3

30

35

10

8

AHP30B**H21

4HK06501025

23.1

26.8

30.8

30

35

10

8

4HK065N1525

34.7

40.0

46.1

40

50

8

8

AHP36C**H21

4HK06501025

23.1

27.5

31.6

30

35

10

8

4HK06501525

34.7

40.0

46.1

40

50

8

8

AHP42C**H21

4HK06501025

23.1

29.1

33.4

30

35

10

8

4HK06501525

34.7

41.6

47.9

50

50

8

8

4HK06501825

41.4

48.9

56.3

50

60

8

6

AHP48D**H21

4HK06501025

23.1

29.3

33.6

30

35

10

8

4HK06501525

34.7

41.8

48.1

50

50

8

8

4HK06501825

41.4

49.0

56.5

50

60

8

6

AHP60D**H21

4HK06501025

23.1

34.5

38.4

35

40

8

8

4HK06501525

34.7

47.0

52.9

50

60

8

6

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

Models

Heater

Model

Minimum Circuit Ampacity

Max. O.C.P.

1

Amps/Type

75°C Wire Size - AWG

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

AHP60D**H21

4HK16501825

31.9/35.4

22.4/25.9

–/–

35/40

25/30

–/–

8/8

10/10

–/–

4HK16502525

40.8/45.6

31.3/36.1

–/–

45/50

35/40

–/–

8/8

8/8

–/–

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

COOLING MODELS WITH ELECTRIC HEAT WIRING

MA SERIES - Air Handler Control Wiring

Typical A/C - Cooling only Applications

THERMOSTAT

AIR HANDLER

BOARD

1 - STAGE

AIR CONDITIONING

R

R

G

Y

W1

W2

C

G

W1

W2

Y

C

Y / Y2

Y1

O

HUM

X / L

COM

HUMIDISTAT *

THERMOSTAT

AIR HANDLER

BOARD

1 - STAGE

AIR CONDITIONING

R

R

G

Y

W1

W2

C

G

W1

W2

Y

C

Y / Y2

Y1

O

HUM

X / L

COM

HUMIDISTAT *

MA SERIES - Air Handler Control Wiring

Typical A/C with Electric Heat Applications