4

Unitary Products Group

FIELD INSTALLED ACCESSORIES

Refer to price manual for specific model numbers:
Start Assist Kit, Time Delay Kit, Electric Heater Kit and Wall
Thermostat.

Electric Heater Kit - Available in 3 different Kw capac-
ities (5, 10, 15 Kw).
Wall Thermostat - The units are designed to operate
with 24-volt electronic and electric-mechanical thermo-
stats.

CONDENSER FAN DATA

MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

RPM

1,100

1,100

1,100

HP

1/3

1/3

1/3

Nameplate FLA

1.8

1.8

1.8

Dia. / No. Blades

18 / 3

20 / 4

20 / 4

CFM @ 0 S.P.

2,300

3,000

3,000

EVAPORATOR COIL DATA

MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

Face Area (Sq. Ft.)

3.61

4.67

4.67

Tube Dia. Ins.

5/16

5/16

3/8

Rows Deep

3

4

4

Fins / Inch

14

12

12

Orifice

.071

.079

.081

EVAPORATOR BLOWER DATA

MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

Motor HP -- RPM

3/4 -- 1,000

3/4 -- 1,050

3/4 -- 1,100

Static Pressure
(Inches Water)

.5

.5

.5

Blower Wheel
Dia. x Width
Rated CFM

10 x 7

1,200

10 x 7

1,500

10 x 7

1,600

Nameplate FLA

3.0

3.0

3.0

ELECTRICAL DATA - for Heat Packages Only

HEATER NUMBER

7642-8051 (5.0 KW) 7642-8101 (10.0 KW) 7642-8151 (15.0 KW)

Heater Branch Circuit Electrical Service

2 Leads + 1 Ground

2 Leads + 1 Ground

2 Leads + 1 Ground

Output Capacity

415 VAC

CAPACITY

17,000

34,100

51,1000

KW

5.0

10.0

15.0

380 VAC

CAPACITY

15,600

31,200

46,800

KW

4.6

9.2

13.7

Circuit Number

1

1

1

Nominal Circuit Load - Amps

12.1

24.1

36.2

Heater Circuit Maximum Fuse Size

20

35

45

Minimum Circuit Ampacity

15.9

27.9

40.0

Maximum wire Size
(60° C) CU

0 - 50 Ft.

12

10

8

51 - 100 Ft.

10

8

6