Charger output voltages – Xantrex Technology PROSINE PS3.0 User Manual
Page 97
80
Prosine 2.5/3.0 Installation & Operation Guide
Charger Output Voltages
GENERAL
Prosine 2.5 12-volt;
(24-volt in parenthesis)
Prosine 3.0 12-volt;
(24-volt in parenthesis)
Transfer Time Inverter to AC
zero seconds, [8 second
delay]
zero seconds, [8 second
delay]
Transfer Time AC to Inverter
(including detect time)
20 milliseconds
20 milliseconds
Regulatory Approvals
CSA/NRTL approved to CSA
107.1, UL 458 and UL 1741,
FCC Class A
CSA/NRTL approved to CSA
107.1, UL 458 and UL 1741,
FCC Class A
Dimensions (L x W x H)
20” x 15” x 5.5”, 508mm x
381mm x 140mm
20” x 15” x 7.0”, 508mm x
381mm x 178mm
Weight
32 lbs, 14.5 kg
32 lbs, 14.5 kg
Operating Temperature
Range (power derating above
25°C)
0-60°C Inverter mode,
0-50°C Charger mode
0-60°C Inverter mode,
0-50°C Charger mode
Storage Temperature Range
-30°C to 70°C
-30°C to 70°C
Absorption / Float Voltage
(Volts)
Cold
Warm
Hot
Flooded
14.8 / 13.9
14.4 / 13.5
14.0 / 13.1
Gel
14.6 / 14.2
14.4 / 13.8
13.8 / 13.4