background image

Error Code Table

90

Prosine 2.5/3.0 Installation & Operation Guide

002

Battery Voltage is too low

1. Discharged battery.
2. Old or faulty battery.

3. Battery cables to the Pros-

ine inverter/charger are too
small, too long, or there is a
loose connection.

1. Charge battery.
2. Battery may not be hold-

ing charge properly. If
flooded, check electro-
lyte level and fill with dis-
tilled water if necessary.
Equalization may help if
recommended by the bat-
tery manufacturer. Battery
may be faulty and require
replacement.

3. Check cable size and

length against recom-
mendations in this man-
ual. Check and tighten all
connections. Large loads
may draw the voltage
down very quickly on a
small battery or in an
installation with cables
that are too small or too
long.

003

Battery Voltage is too high.

1. External charger or alterna-

tor has output voltage
greater than 16 V.

2. A 12V Prosine inverter/

charger could be connected
to a 24V battery (two batter-
ies in series).

1. Correct or disconnect the
external charging source.

2. Make sure the battery
bank is nominal 12V for a
12v Prosine.

006,065

Microprocessor communi-
cation error.

Remote display cable is
pinched or has loose connec-
tion.

Check display cable con-
nections and attempt
restart. If the problem per-
sists, try a replacement
cable.
If the problem persists, call
Xantrex.

Error
Code

Description of Fault

Possible Cause

Solution