Prosine 2.5/3.0 Installation & Operation Guide

89

Appendix C: Troubleshooting

Error Code Table

The following table lists the error codes, likely causes, and suggested solutions.

Error
Code

Description of Fault

Possible Cause

Solution

000, 255

No Fault recorded

No faults detected since the
Prosine was turned on.

001

A. Battery Temperature is

too high or too low. (This
code only applies if the
external battery tempera-
ture sensor is connected)

B. If there is no external

battery temperature sen-
sor, there may be a wiring
fault inside the unit.

1. Room temperature around

the batteries is too high or
too low.

2. Battery heating (battery or

battery terminals are
warmer than room tempera-
ture

3. Faulty connection of battery

temperature probe.

B. Damage has likely

occurred during shipping or
there has been extreme
shock or vibration.

1. Keep the temperature

around batteries moder-
ate. In cold weather, try a
battery heating blanket.
In warm weather, try
improving the ventilation.

2. For flooded batteries,

check the electrolyte level
and top up with distilled
water if necessary. Check
the tightness of all con-
nections. If the condition
persists, the battery may
be faulty and need
replacement.

3. Check connections and

make sure probe is in
good thermal contact with
battery. Probe may
require replacement.

B. Record the error code

and contact Xantrex.