York AFFINITY R-410A User Manual
Page 13

333495-YTG-C-0908
Johnson Controls Unitary Products
13
115°F
125°F
750
77
29.2
3.1
13.8
10.2
6.7
-
-
-
26.0
3.3
12.5
8.9
5.3
-
-
-
72
26.4
3.1
18.6
15.1
11.5
7.9
-
-
23.4
3.4
17.5
13.9
10.4
6.8
-
-
67
23.7
3.2
23.5
19.9
16.3
12.8
9.2
-
20.8
3.5
20.8
19.0
15.4
11.8
8.3
-
62
22.1
3.1
22.1
21.7
18.1
14.6
11.0
7.4
20.5
3.4
20.5
20.2
16.6
13.1
9.5
5.9
57
20.2
3.1
20.2
20.2
16.6
13.0
9.5
5.9
17.2
3.4
17.2
17.2
13.9
10.4
6.8
3.2
875
77
29.3
3.1
18.7
12.0
7.4
-
-
-
26.2
3.4
18.2
10.9
6.0
-
-
-
72
26.5
3.2
21.1
16.9
12.7
8.5
-
-
23.5
3.5
20.0
15.8
11.6
7.4
-
-
67
23.7
3.3
23.6
21.8
18.1
13.9
9.6
-
20.9
3.6
20.9
20.7
17.2
13.0
8.8
-
62
22.2
3.2
22.2
22.0
20.1
15.8
11.6
7.4
20.6
3.5
20.6
20.5
18.6
14.3
10.1
5.9
57
20.3
3.2
20.3
20.2
18.4
14.2
9.9
5.7
17.3
3.5
17.3
17.3
15.6
11.4
7.2
2.9
1000
77
29.3
3.2
23.6
13.8
8.1
-
-
-
26.3
3.4
24.0
12.8
6.6
-
-
-
72
26.5
3.2
23.7
18.8
13.9
9.1
-
-
23.7
3.6
22.5
17.6
12.8
7.9
-
-
67
23.8
3.3
23.8
23.8
19.8
15.0
10.1
-
21.0
3.7
21.0
21.0
19.0
14.1
9.2
-
62
22.2
3.2
22.2
22.2
22.0
17.1
12.3
7.4
20.7
3.5
20.7
20.7
20.5
15.6
10.8
5.9
57
20.3
3.3
20.3
20.3
20.1
15.3
10.4
5.6
17.4
3.6
17.4
17.4
17.2
12.4
7.5
2.6
1125
72
28.6
3.3
26.5
21.0
15.4
9.9
-
-
26.9
3.6
25.5
20.0
14.4
8.9
-
-
67
25.6
3.4
25.6
25.6
21.9
16.4
10.9
-
24.0
3.7
24.0
24.0
21.3
15.8
10.3
-
62
23.9
3.3
23.9
23.9
23.8
18.3
12.7
7.2
23.5
3.6
23.5
23.5
23.3
17.8
12.3
6.7
57
21.9
3.3
21.9
21.9
21.8
16.2
10.7
5.2
19.9
3.6
19.9
19.9
19.8
14.3
8.8
3.2
1250
72
30.6
3.4
29.4
23.1
16.9
10.7
-
-
30.2
3.6
28.5
22.3
16.1
9.8
-
-
67
27.4
3.5
27.4
27.4
24.1
17.9
11.6
-
26.9
3.8
26.9
26.9
23.7
17.5
11.3
-
62
25.6
3.4
25.6
25.6
25.6
19.4
13.2
7.0
26.2
3.6
26.2
26.2
26.2
20.0
13.8
7.6
57
23.4
3.4
23.4
23.4
23.4
17.2
11.0
4.8
22.4
3.7
22.4
22.4
22.4
16.2
10.0
3.8
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
BHZ030 (2.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Net
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65