Some installations may require a locking cover to protect the

thermostat from tampering and/or damage.

Both the manual and auto changeover thermostats have non-

adjustable, voltage-type anticipators for both cooling and heat-

ing.

WIRE SIZING

Refer to the following chart to size the control wiring properly. If

the wiring is undersized,voltage drop could become excessive

and result in malfunctioning of the unit controls.

REFRIGERANT PIPING
GENERAL GUIDELINES

Many service problems can be avoided by taking adequate

precautions to provide an internally clean and dry system and

by using procedures and materials that conform with estab-

lished standards.

Unitary Products Group

5

035-15410-002-B-0404

FIG. 3 - TYPICAL FIELD WIRING

Model

EFB

Compressor

Outdoor Fan Motor

Min.

Circuit

Amps

Max.

Fuse

Size

Power

Supply

RLA

LRA

Power

Factor

Power

Supply

Qty.

FLA

(Each)

E3FB

090A

25 200/230-3-60

25.6

180.0

0.94 @ 208V

208/230-1-60

1

3.03

35.1

60

0.84 @ 230V

46 460-3-60

13.5

95.0

0.86

460-1-60

1

1.6

18.4

30

50 308/415-3-50

13.5

85.0

0.86 @ 380V

380/415-1-50

1

1.6

18.4

30

0.79 @ 415V

E2FB

120A

25 208/230-3-60

42.0

239.0

0.91 @ 208V

208/230-1-60

2

2.7

51.8

70

0.82 @ 230V

46 460-3-60

19.2

125.0 0.82

460-1-60

2

1.6

24.7

35

50 380/415-3-50

19.6

118.0

0.87 @ 380V

380/415-/-50

2

1.6

25.2

35

0.80 @ 415V

1

Based on three, 60°C insulated copper conductors in steel conduit.

2

Based on a 3% voltage drop.

TABLE 3

- ELECTRICAL DATA

RECOMMENDED

WIRE SIZE

MAXIMUM TOTAL

CIRCUIT LENGTH - FT.*

#19 Solid

#18 Solid

130

170

#18 Stranded

#16 Stranded

180

270

#14 Stranded

#12 Stranded

455

730

*

To determine the total circuit length, add the following distances:

1 - Outdoor Unit to Indoor Unit................................

____________

2 - Indoor Unit to Thermostat...................................

____________

3 - Thermostat to Indoor Unit...................................

____________

2 - Indoor Unit to Outdoor Unit................................. ____________

Total Circuit Length............ ____________

Note: Refer to document 036-13335-003

for correct thermostat.