beautypg.com

Operation – York E2FB120 User Manual

Page 13

background image

GENERAL

During the cooling cycle, when the reversingvalve solenoidbe-

comes energized, operation will be the same as any conven-

tional air conditioning system.
During the heating cycle, when the reversing valve solenoid

becomes de-energized, compressor discharge gas will be di-

verted to the indoor coil and the outdoor coil will become the

evaporator.
Refer to Figure 7 for illustration showing the flow of refrigerant

through a heat pump system.
CAUTION: Reversing valves and check valves are precise

mechanical devices and will not tolerate any me-

chanical abuse such as hammering. If a refrigerant

system isn't properly cleaned after a compressor

burn-out, scale may build up at these devices and

prevent them from operating properly.

SYSTEM SEQUENCE OF OPERATION

The following sequences of operation are based on using the

manual changeover thermostat. Refer to the respective unit

wiring diagram.

COOLING OPERATION

1. The following controls will be energized through terminal O

on the thermostat to put the system in the cooling mode.

The reversing valve solenoid (7-1/2 Ton units)

Relay 2R and the reversing valve solenoid (10 Ton units)

2. If the fan switch on the thermostat is in the “ON” position, in-

door section blower motor contactor 10M will be energized

through terminal G to provide continuous blower operation.

If the switch is in the “AUTO” position, the blower will oper-

ate only when the thermostat calls for cooling operation.

3. When TC1 of the thermostat closes on a demand for cool-

ing, a circuit is made from terminal Y through the defrost

control board and safety switches to energize contactor 1M

and relay 1R, starting the compressor. Contactor 2M is en-

ergized through the NO contacts of 1R-2 and the NC con-

tacts of K2 on the defrost control board in order to start the

outdoor fan motor(s).

NOTE: On 10 Ton units, both outdoor fan motors will oper-

ate if the ambient temperature is above 65 °F. If the

ambient temperature falls below 65 °F, control 3TH

will shut down the No. 1 fan motor.

4. Relay 1R also prevents the 10KW portion of accessory

electric heat referenced as standby electric heat from being

utilized whenever the compressor is in operation. This part

of the circuit is covered under HEATING OPERATION.

5. The thermostat will cycle the unit to satisfy the cooling re-

quirements of the conditioned space.

6. After the unit has shutdown from a cooling cycle or a power

interruption, the anti-short cycle feature of the defrost con-

trol board will not permit the unit to restart for 5 minutes.

This feature prevents the unit from short cycling.

7. If the discharge pressure reaches 430 psig, the HP control

will open and the defrost control board will lock out the com-

pressor. If the discharge temperature reaches 255°F, 2TH

thermostat will open and the defrost control board will lock

out the compressor. If the suction pressure falls to 7 psig,

the low pressure switch will open and the defrost control will

lock out the compressor.

8. If the control that caused the lockout has automatically re-

set, the unit can be restarted by one of the following:

a. Turning the system switch on the thermostat to the

“OFF” position and back to the “COOLING” position.

b. Increasing the set point on the thermostat above the

temperature in the conditioned space and then return-

ing it to its original setting.

c. Opening and closing the power supply main disconnect

switch.

IN ALL THREE RESET METHODS DESCRIBED ABOVE,
A FIVE MINUTE TIME DELAY WILL TAKE PLACE AFTER
THE RESET BEFORE THE UNIT WILL RESTART.

HEATING OPERATION

1. Reversing valve is de-energized and the system will be in

the heating mode.

2. If the fan switch on the thermostat is in the “ON” position, in-

door section blower motor contactor 10M will be energized

through terminal G to provide continuous blower operation.

If the switch is in “AUTO” position, the blower will operate

only when thermostat calls for heating operation.

3. When TH1 of the thermostat closes for first-stage heat, a

circuit is made from terminal Y through the defrost control
board and safety switches to energize contactor 1M and
start the compressor. Contactor 2M is energized through
the NO contacts 1R-2 and the NC contacts of K2 on the de-
frost control board which will start the outdoor fan motor(s).

NOTE: On 10 Ton units, if 3TH thermostat opens due to

outdoor ambient temperature being below 65 °F,

the No. 1 fan motor will continue to operate through

the NC contacts of relay 2R.

4. The thermostat will cycle the unit to satisfy the heating re-

quirements of the conditioned space.

5. After the unit has shutdown from a heating cycle or a power

interruption, the anti-short cycle feature of the defrost con-

trol board will not permit the unit to restart for 5 minutes.

This feature prevents the unit from short cycling.

6. If the discharge pressure reaches 430 psig, the HP control

will open and the defrost control board will lock out the com-
pressor. If the discharge temperature reaches 255°F, 2TH

thermostat will open and the defrost control board will lock

out the compressor. If the suction pressure falls to 7 psig,

the low pressure switch will open and the defrost control will

lock out the compressor.

7. If the control that caused the lockout has automatically re-

set, the unit can be restarted by one of the following:

a. Turning the system switch on the thermostat to the

“OFF” position and back to the “HEATING” position.

b. Decreasing the set point on the thermostat below the

temperature in the conditioned space and then return-

ing it to its original setting.

c. Opening and closing the power supply main disconnect

switch.

035-15410-002-B-0404

Unitary Products Group

13

OPERATION

This manual is related to the following products: